Rated capacity:
544 KW
Rated capacity in kVA:
680 kVA
Output voltage:
400 V
Execution:
Aggregate type:
stationary
Execution:
Soundproofed
Technical data engine:
Engine manufacturer:
MTU
Engine:
12 V 1600 G 20 F
Engine No.:
in production
Power:
576 KW
Cooling:
Water-cooled
Occasion:
Electric 24 V DC
Speed:
1500 rpm
Fuel:
Fuel oil EN 590
Technical data generator:
Generator manufacturer:
Stamford AvK
Generator type:
synchronous with AVR
Gene. No.:
in production
Generator power:
680 kVA
Voltage:
400 / 231 Volt
Power factor:
Cos. - PHI 0.8
Speed:
1500 rpm
Switchgear:
Execution:
Automatic start
Functions:
Emergency power parallel operation
Switch:
Generator switch 4 poles
Delivery:
Built
Tank:
Execution:
Base frame tank with drip pan
Content / liter:
990
Dimensions of the power unit:
Width approx. mm:
1.850
Height approx. mm:
2.550
Length approx. mm:
4.820
Weight approx. KG:
7.500
Condition:
New
Year of construction:
2023
Delivery period:
08 / 2023
Hours:
1
Location:
Verl - Germany
Scope of delivery:
Pre-order for delivery from August 2023!
Emergency generator as a backup power generator for your reliable
emergency power supply as a backup power system with an MTU industrial
diesel engine from the 1600 series with electronic speed control and
three-phase synchronous generator. The motor and generator are
elastically mounted on a common skid frame. The radiator is pre-built,
fan driven by the diesel engine. Installed in a modular soundproofing
enclosure with generous doors for maintenance. Powder-coated in RAL
9010
Fuel consumption according to the MTU data sheet:
Fuel consumption approx. 50% (PRP) 63 l/h
Fuel consumption approx. 75% (PRP) 90 l/h
Fuel consumption approx. 100% (PRP) 116 l/h
Electronic regulators ECU 8
Precision class control quality: G3
Number of cylinders 12 in V shape
Displacement: 21 litres
Bore / stroke 122 mm x 150 mm
Oil volume 72.5 litres
Radiator water volume 99 litres
Other additional features:
Internal automatic start-stop system (type: Comap Intelygen IG 200)
with display of all important engine and generator messages.
Functional display A5168 digitally on the display. Generator switch
1,000 amperes, 4 poles integrated on the aggregate (generator).
Internal battery charger 230 volts – 24 volts DC
Optionally available at an additional cost:
Automatic start with 4-pole mains and generator switching
External emergency power switchgear for installation in the building
and 4-pole mains generator switching
Function: In the event of a power failure, the start command is
transferred to the diesel generator. When the nominal speed and
nominal voltage are reached, the generator switch is switched on. In
the event of a return to the mains, the automatic system monitors the
mains voltage. If this is stable again, the switchback takes place
WITHOUT INTERRUPTION back to mains operation. The diesel generator is
stopped after the cooling time and waits in automatic mode for the
next power failure.
The emergency generator with MTU engine is currently in production and