Execution:
Aggregate type:
stationary
Execution:
Soundproofed
Technical data engine:
Engine manufacturer:
Deutz
Engine:
F 4 M 2011
Engine No.:
miscellaneous
Power:
27 KW
Cooling:
Oil-cooled
Occasion:
Electric 12 V DC
Speed:
1500 rpm
Fuel:
Fuel oil EN 590
Technical data generator:
Generator manufacturer:
Stamford AvK
Generator type:
Synchronous
Gene. No.:
Miscellaneous
Generator power:
30 kVA
Voltage:
400 / 231 Volt
Power factor:
Cos. - PHI 0.8
Speed:
1500 rpm
Switchgear:
Execution:
Automatic start
Functions:
Remote start
Switch:
Generator switch 4 poles
Delivery:
Built
Tank:
Execution:
Base frame tank with drip pan
Content / liter:
100
Dimensions of the power unit:
Width approx. mm:
960
Height approx. mm:
1.236
Length approx. mm:
2.000
Weight approx. KG:
1.075
Stock number:
1275
Condition:
Demonstration machine
Year of construction:
2022
Delivery period:
Instant Verl
Hours:
2
Location:
Verl - Germany
Scope of delivery:
Emergency power generator as emergency power supply for emergency
power supply as a backup power system with an original Deutz
industrial diesel engine with speed control and Stamford three-phase
synchronous generator. The motor and generator are elastically mounted
on a common skid frame. Installed in a modular soundproofing
enclosure.
Powder-coated in RAL 3000
Other additional features:
Tank capacity 100 litres, refuelling directly at the tank
Fuel consumption at :
100 % load = 6,6 liters / hour
75 % load = 4,8 liters / hour
50 % load = 3.3 litres / hour
Internal automatic start-stop system (type: AMF DSE 4150) with display
of all important engine and generator messages. Functional display
digitally on the display. Generator switch 40 amps 4 poles integrated
on the aggregate (generator). Internal A5168 battery charger 230
volts – 12 volts DC
Optionally available at an additional cost:
Automatic start with 4-pole mains and generator switching
External emergency power switchgear for installation in the building
and 4-pole mains generator switching
Function: In the event of a power failure, the start command is
transferred to the diesel generator. When the nominal speed and
nominal voltage are reached, the generator switch is switched on. In
the event of a return to the mains, the automatic system monitors the
mains voltage. When this is stable again, the switch back to mains
operation takes place. The diesel generator is stopped after the
cooling time and waits in automatic mode for the next power
failure.
The emergency power system as an emergency power supply is ready for