Execution:
Aggregate type:
stationary
Execution:
Super soundproofed
Technical data engine:
Engine manufacturer:
Deutz AG
Engine:
BF 4 M 1013 EC
Engine No.:
on request
Power:
93 KW
Cooling:
Water-cooled
Occasion:
Electric 12 V DC
Speed:
1500 rpm
Fuel:
Fuel oil EN 590
Technical data generator:
Generator manufacturer:
Stamford AvK
Generator type:
Sychron with AVR
Gene. No.:
on request
Generator power:
100 kVA
Voltage:
400 / 231 Volt
Power factor:
Cos. - PHI 0.8
Speed:
1500 rpm
Switchgear:
Execution:
Automatic start
Functions:
Emergency power operation
Switch:
Generator switch 4 poles
Delivery:
Built
Tank:
Execution:
Base frame tank with drip pan
Content / liter:
270
Dimensions of the power unit:
Width approx. mm:
1.080
Height approx. mm:
1.910
Length approx. mm:
2.980
Weight approx. KG:
1.685
Condition:
New
Year of construction:
2023
Delivery period:
Instant Verl
Hours:
1
Location:
Verl - Germany
Scope of delivery:
Emergency power system, emergency power supply as backup power supply
with a Deutz industrial diesel engine with mechanical speed control
and cooling water preheating (230 volts) and three-phase synchronous
generator. The motor and generator are elastically mounted on a common
skid frame.
Other additional features:
Tank capacity 270 litres, refuelling directly at the soundproofing
hood
Fuel consumption at 50% load 12 litres/hour, sufficient for approx.
22.5 hours of operation
Fuel consumption at 100% load 23 litres/hour, sufficient for approx.
11.7 hours of operation
Internal automatic start-stop system (type: Comap AMF 25) with display
of all important engine and generator messages. Functional display
digitally on the display. Generator switch 4 poles integrated on the
aggregate (generator). Internal battery charger 230 volts – 12
A5368 volts DC
Automatic start with 4-pole mains and generator switching
Optional: External emergency power switchgear for installation in the
building and 4-pole mains generator switching with the following
dimensions: Height: 700 mm Width: 500 mm Depth: 270 mm
Function: In the event of a power failure, the start command is
transferred to the diesel generator. When the nominal speed and
nominal voltage are reached, the generator switch is switched on. In
the event of a return to the mains, the automatic system monitors the
mains voltage. When this is stable again, the switch back to mains
operation takes place. The diesel generator is stopped after the
cooling time and waits in automatic mode for the next power
failure.
The emergency power system as an emergency power supply is ready for
operation and immediately available from the Verl warehouse.