Execution:
Aggregate type:
stationary
Execution:
Soundproofed
Technical data engine:
Engine manufacturer:
Baudoin
Engine:
12 M 33 G 1400 / 5
Engine No.:
in production
Power:
1,100 KW
Cooling:
Water-cooled
Occasion:
Electric 24 V DC
Speed:
1500 rpm
Fuel:
Fuel oil EN 590
Technical data generator:
Generator manufacturer:
Stamford AvK
Generator type:
PI 734 B
Gene. No.:
in production
Generator power:
2,000 kVA
Voltage:
400 / 231 Volt
Power factor:
Cos. - PHI 0.8
Speed:
1500 rpm
Switchgear:
Execution:
Automatic start
Functions:
Emergency power operation
Switch:
Generator switch 4 poles
Delivery:
Built
Tank:
Execution:
Base frame tank with drip pan
Content / liter:
1000
Dimensions of the power unit:
Width approx. mm:
2.460
Height approx. mm:
3.730
Length approx. mm:
9.620
Weight approx. KG:
16.700
Stock number:
1263
Condition:
Demonstration machine
Year of construction:
2023
Delivery period:
3 months
Hours:
2
Location:
Verl - Germany
Scope of delivery:
Emergency power system as an emergency power generator for your
reliable emergency power supply as a backup power system with a
Baudouin industrial diesel engine with electronic speed control and
Stamford three-phase synchronous generator. The motor and generator
are elastically mounted on a common skid frame. The radiator is
pre-built with an electric motor. Installed in a modular soundproofing
enclosure. Powder-coated in RAL 9010
Consumption according to Baudoin data sheet
Fuel consumption approx. 50% (PRP) 129 l/h
Fuel consumption approx. 75% (PRP) 180 l/h
Fuel consumption approx. 100% (PRP) 258 l/h
Electronic regulators standard
Precision class control quality: G3
Number of cylinders 12 in V shape
Displacement: 39.2 litres
Bore / stroke 150 mm x 185 mm
Oil quantity 160.0 litres
Radiator water volume 240 litres
Exhaust gas temperature 550 °C
Exhaust gas flow 237 m³/min
Cooling air requirement 108,765 m³/min
Combustion air requirement 4,926 m³/min
Other additional features:
Internal automatic start-stop system (type: AMF 25) with display of
all important engine and A5168 generator messages. Functional display
digitally on the display. Generator switch 40 amps 4 poles integrated
on the aggregate (generator). Internal battery charger 230 volts –
12 volts DC
Optionally available at an additional cost:
Automatic start with 4-pole mains and generator switching
External emergency power switchgear for installation in the building
and 4-pole mains generator switching
Function: In the event of a power failure, the start command is
transferred to the diesel generator. When the nominal speed and
nominal voltage are reached, the generator switch is switched on. In
the event of a return to the mains, the automatic system monitors the
mains voltage. When this is stable again, the switch back to mains
operation takes place. The diesel generator is stopped after the
cooling time and waits in automatic mode for the next power
failure.
The emergency power system as an emergency power supply is currently
in production and will be available at short notice.